CT's are categorized as Protection CT, Special Protection 
CT and Measuring CT. Based on this, the CT's are 
classified. Here is the meaning of the CT classes:

Class 5P20: 

The letter 'P' indicates it is a protection CT.

The number 5 indicates the accuracy of the CT. It means 5% secondary current error at 100% primary current. Most common accuracy numbers are 5 and 10.

The number 20 (called accuracy limit factor) indicates that 
the CT will sense the current with the specified accuracy 
even with 20 times of its secondary current flows in the 
secondary. This is required for protection CT, because the 
fault current is high and the CT should be able to sense 
the high fault current accurately to protect the system. 
The common numbers are 10, 15, 20 and 30.

Class PS:

PS is for 'Protection Special'. This class of CT's are used 
for special protection such as differential protection, 
distance protection etc.

Class 1M:

The letter 'M' indicates it is a measuring CT.

The number 1 indicated the accuracy of the CT. The 
measuring CT's should be more accurate than the protection 
CT. The most common accuracy numbers are 0.5 and 1.

Measuring CT's are intended to work in normal and it 
doesn't require working with accuracy beyond the CT 
secondary current rating, so the accuracy limit factor is 
not mentioned here. 

CT 0.2 is having a secondary current error of 0.2% at 100% of primary current and 0.75% error @ 5% of primary current. It is used for standard revenue metering.

CT 0.2s(special) is having a secondary current error of 0.2% at 100% of primary current, 0.35% error @ 5% of primary current and 0.75% error @ 1% of primary current. It is used for Precision revenue metering.

CT 0.5 is having a secondary current error of 0.5% at 100% of primary current and 1.5% error @ 5% of primary current. It is used for standard commercial metering.

CT 0.5s(special) is having a secondary current error of 0.5% at 100% of primary current, 0.75% error @ 5% of primary current and 1.5% error @ 1% of primary current. It is used for Precision commercial metering.