Sunday 4 September 2022

In brushless generator what happens if diode short circuits or open circuits?

If a rectifier diode shorts, a very high current flows through the associated exciter winding thus causing excessive heating and probable failure of the exciter.

The voltage regulator may fail due to high voltage ripple reflected back through the exciter field.


If a rectifier diode opens, the voltage regulator will substantially increase the excitation.

Why one end of Current transformer (CT) is earthed?

If the CT secondary winding is not grounded, the capacitive coupling between primary and secondary could allow the CT secondary voltage to float up to the voltage of the mains.

This is a serious safety hazard.

The effects of changing the supply frequency of an induction motor.

 1. Rotational speed is a direct function of frequency.

2. Cooling fan speed is a direct function of rotational speed.

3. Back emf decreases as the motor slows down.

4. Current increases with reduced back emf.

5. The magnetic capacity of the motor's magnetic circuit is designed to the relationship: Voltage/frequency ( V/f ).

            If the frequency drops, then the V/f ratio goes up. This means that the magnetic flux increases and the motor needs a larger magnetic circuit. Without it, the magnetic circuit can become overloaded. This is called saturation and it leads to a rapid increase in current draw and a corresponding large increase in temperature.

            If the frequency increases, the V/f ratio drops with no issues as the magnetic circuit will remain plenty large enough for the magnetic flux. But the motor may have a worse power factor.



Explosion protection for electrical equipment

 Electrical equipment is defined and certified as explosion proof when it is enclosed in a case, which is capable of withstanding the explosion within it of a hydrocarbon gas/air mixture or other specified flammable gas mixture. 

It must also prevent the ignition of such a mixture outside the case either by spark or flame from the internal explosion or as a result of the temperature rise of the case following the internal explosion. 

The equipment must operate at such an external temperature that a surrounding flammable atmosphere will not be ignited.

Types of explosionproof protections

Ex i                 -           Intrinsically safe

Ex m               -           Encapsulated

Ex e                -           Increased safety

Ex d                -           Flameproof

Ex p                -           Pressurized

Ex v                -           Ventilated   

Ex n                -           Non sparking

Ex nC              -           Non incendive

Ex nR              -           Restricted breathing

Ex o                -           Liquid immersion

Ex q                -           Powder filling

Ex h                -           Constructional safety

Ex t                 -           Protection by enclosures

Ex fr               -            Flow restricting


Flameproof - I this type of protection the enclosure which houses the electrical equipment is designed in a manner that the explosion inside the enclosure due to ingress of explosive/flammable gas or vapor will not be transmitted/communicated to outside hazardous atmosphere. 

Intrinsically safe - In this type of protection the equipment is designed in such a manner that the electrical energy which can enter explosive environment is so low or restricted in a manner that it cannot ignite an explosive gas air mixture.


Zone classification

It is based on the likelihood and the duration of an explosive atmosphere.

Zone classification for flammable gases is divided into Zone 0, Zone 1, Zone 2 and for combustible dusts Zone 20, Zone 21, Zone 22.

Zone 0

Ex ia, Ex ma, Ex ta, Ex da, Ex h

Place in which an explosive atmosphere consisting of a mixture with air of flammable substance in the form of gas, vapor or mist is present continuously for long periods or frequently. Generally, it is limited to confined spaces.

Zone 1

Ex ib, Ex mb Ex tb, Ex db, Ex h, Ex eb, Ex ob, Ex p, Ex q, Ex v

Place in which an explosive atmosphere consisting of a mixture with air of flammable substance in the form of gas, vapor or mist is likely to occur in normal operation occasionally.

Zone 1 usually includes locations where volatile flammable liquid or liquified gases are transferred, gas generator rooms, pump rooms etc.

Zone 2

Ex ic, Ex mc, Ex tc, Ex dc, Ex h, Ex ec, Ex nC, Ex nR, Ex oc, Ex p, Ex fr, Ex v, Ex n

Place in which an explosive atmosphere consisting of a mixture with air of flammable substance in the form of gas, vapor or mist is not likely to occur in normal operation but if it does occur, will persist for a short period only.

Complete segregation from Zone 1 location. Well ventilated and can rapidly disperse the abnormal gas concentrations.


Gas group

Electric equipment for hazardous gas areas is grouped as:

Group I   -    for mines susceptible to methane

Group II  -    for all places with an explosive gas atmosphere except mines susceptible to methane

                    Group II is further divided into IIA, IIB and IIC.

                    I        Methane

                    IIA    Propane

                    IIB    Ethylene

                    IIC    Hydrogen


Temperature rating

Electrical apparatus must be selected so that the maximum surface temperature that could cause an ignition of the flammable product is not exceeded.

                    rating          max surface temperature

                        T1                            450 degC

                        T2                            300 degC

                        T3                            200 degC

                        T4                            135 degC

                        T5                            100 degC

                        T6                            85 degC

Saturday 3 September 2022

The effect of change in fuel supply when generators are in parallel

 

Since the speeds of the two machines are tied together by their synchronous bond, the increase in fuel to the machine 1 does not make it run faster. 

Alternatively, it utilises the increased power input for carrying more load than machine 2.

This is possible because of angular advance of machine 1 with respect to machine 2. 

Here E1 advances E2 by an angle αThe resultant voltage Er sets up a current Isy which is almost in phase with E1

Hence, power per phase of machine 1 is increased by an amount =E1 Isy whereas that of machine 2 is decreased by the same amount. 

Since Isy has no reactive component, the increase in fuel supply does not disturb the division of KVAR but it increases KW of machine 1 and decreases that of machine 2.








The effect of change in excitation / different generator voltages when in parallel

Suppose the initial operating conditions of the two identical alternators in parallel with KW and KVAR load being shared equally, thus operating in same power factor. Each machine supplies a load current I so that total output current is 2I


If excitation of alternator No.1 increases, then E1 increases than E2. This difference sets up a circulating current Ic = E1 - E2 / 2Zs which is confined to the local path through the stator and the busbars. 

This current is superimposed on the original current. The Ic is added as a vector to the machine No.1 current I and subtracted from machine No.2 current I

Now the two machines deliver I1 and I2 current at respective power factors cosø1 and cosø2. The cosø1 reduces and cosø2 increases. 

So, the effect of KW loading is negligible but KVAR1 & current supplied by machine No.1 increases and KVAR2 & current supplied by machine No.2 decreases.














Thursday 18 August 2022

GMDSS Battery capacity test

Regulation for Radio battery capacity test

6.   Where a reserve source of energy consists of a rechargeable accumulator battery or batteries: 

.1   a means of automatically charging such batteries shall be provided which shall be capable of recharging them to minimum capacity requirements within 10 h; and 

.2   the capacity of the battery or batteries shall be checked, using an appropriate method, at intervals not exceeding 12 months, when the ship is not at sea.

 (SOLAS 1974, as amended, regulation IV/13)


7.4.6   The capacity of the radio batteries should be checked at intervals not exceeding 12 months when the ship is not at sea. One method of checking the capacity is to fully discharge and recharge the batteries using normal operation current over a period of 10 hours. Assessment of the charge condition can be made at any time, but it should be done without significant discharge of the battery when the ship is at sea. Another method could be to check the capacity by means of a battery tester, e.g., in connection with a radio survey. (SOLAS 1974, as amended, regulation IV/13, IMO resolution A.702(17) and COMSAR/Circ. 16)

Note: - When determining the battery capacity, the following should also be taken into consideration:

- the battery is normally not fully charged.
- reduction of capacity due to ageing.
- reduction of capacity due to high or low temperatures; and
- reduction of capacity due to rapid discharge.

                                                                                                                                (COMSAR/Circ.32, ANNEX, Page 33)


Radio battery capacity requirement

7.4.4   If the capacity requirement of radio batteries is to be maintained over their normal life cycle, an extra 40% capacity should be added to the minimum calculated capacity.

                                                                       (COMSAR/Circ.32, Annex, page 32)


2.2   For guidance, the nominal battery capacity to comply with the minimum capacity requirements at all times is 1.4 times the load determined in paragraph 2.4 multiplied by the intended period of operation (1 hour or 6 hours in accordance with SOLAS IV/13.2).

                                                         (COMSAR/Circ.16, Annex, page 4)


Key terminologies to understand:

minimum capacity requirement = load determined for the radio system x 1hr or 6hr

Most of the ships are required to have only 1hr intended period of operation.

hence, minimum capacity requirement = load determined for the radio system.

nominal battery capacity = 1.4 x minimum required capacity 

The installed battery capacity will be equal to or greater than the nominal battery capacity, whichever is available in the market.

The minimum required capacity can be safely taken as 72% of the installed battery capacity.


The radio battery capacity should not be less than the minimum required capacity at any time. The annual battery capacity test is being carried out to ascertain whether the present battery capacity is higher than the minimum required capacity or not. During charging cycle after the capacity test, the battery should be charged to minimum required capacity in 10hrs. However, the battery requires more hours of charging to get it fully charged.


The capacity of a lead acid battery is normally quoted at 20 hours of discharge at an operational temperature of 20°C. But in general, most of the lead acid batteries having capacity of 100Ah or more can deliver the battery capacity in 10 hours of discharge. Battery capacity will decrease over the period of time due to various factors. Hence the battery capacity needs to be checked.


Consider if a radio battery of 200Ah, 12V, 02nos are in use:

for 10 hours discharge, we need 20A constant discharge (200 / 10 = 20A).

But the current will be decreasing rather being constant due to decreasing battery voltage and increasing internal resistance. The rate of current decrement is related the health of the battery.

For a 20A current discharge we need a 24V lamp load of 480W (20A x 24V) which can be made with 8nos 60W,24V lamps.

So, we can prepare a lamp load bank of 24V, 60W, 8nos for capacity test with each lamps having its own switch.


Disconnect the battery from the system and the charger.

Connect the load bank to the battery through a switch or breaker.

Connect a multimeter across the battery terminal to measure the battery voltage.

Connect a DC clamp meter to the load bank.

Switch on all 8nos individual lamp switches and then switch on the main breaker of load bank.

Immediately note down the voltage and current. 

Continue to note down the voltage and current every minute for next five minute. In this five minute, the battery voltage will dip and rise which will indicate the general health of the battery. A good battery will have a shallow dip and will rise soon.

Continue to note down the voltage and current every half an hour until the battery voltage drops to 21.12V, 88% (1.76V x 12cells). The safe discharge voltage of a cell according to most of the makers is 1.75V (end cell voltage). SOLAS chapter IV does not say anything about how much should be the maximum voltage drop while discharging. However, following can be considered for any battery; as per SOLAS Reg II-1/13-4, a battery "which shall operate without recharging while maintaining the voltage of the battery throughout the discharge period within 12% above or below its nominal voltage". The 12% drop of a cell voltage resulted to be 1.76V and it will be 21.12V (88%) for the battery. 

Calculate the Ah discharged (current x time) for every half an hour and add all to get the total discharged Ah.

Calculate the battery % capacity with respect to nominal battery capacity.

Disconnect the load bank and connect the battery to the charger.

Connect the multimeter and DC clamp meter accordingly.

Switch on the charger and note down the voltage and current.

Continue to note down the voltage and current every hour for next 10hrs.

Connect the battery to the system and keep charger on. The battery will continue charging. The automatic battery chargers will not charge the battery to its nominal value in 10hrs. The charger will control the charging current throughout to avoid any battery damage. However, the charger can easily charge the battery more than the minimum required capacity in 10hrs which is required by SOLAS if the battery is good.

Calculate the Ah charged which should be more than the minimum required capacity.

Plot the discharging and charging parameters on graph for record keeping.

If the battery capacity is less than 80% or the Ah charged in 10hrs is less than minimum required capacity, then initiate the battery replacement procedure.


Capacity test can be carried out at PORT or at anchorage inside port limit while awaiting berth & not proceeding/waiting for sea passage as per Singapore flag state. The 10hr charging has to be completed before ship leaves the port.