Why
we use a resistance to ground the neutral when we need always low resistivity
for the grounding?
§ If we ground the
generator directly then whenever a fault will take place at any phase with
ground the fault current flowing throw the faulted phase-to ground-to neutral
will be very high cause there will be no resistance to limit the value of fault
current. Hence we insert a resistance in the neutral circuit to limit this
fault current. Also we need to reduce the fault current to such a value that
the protection CTs are able to identify the fault current without saturating
the CTs. Communicate it to the protection relays & hence the relays can
then isolate the system from the fault; so that the system is isolated from the
fault before the harm is done by the fault current. That is the reason that all
the equipment will be designed for fault KiloAmpere values for 1 sec so that
the total operation(CT sensing-relay functioning-circuit breaker operation )
time will be less than 1 sec. hence the Breakers will isolate the fault before
1 sec i.e. within the time period the equipment are designed to carry the fault
current. Thus all your objectives of:
§ preventing the
arcing.
§ limiting the fault
current.
§ isolating the faulted
system are achieved
No comments:
Post a Comment